How box fill is counted (NEC 314.16(B))
Volume = (conductors + 1 for grounds + 1 for clamps + 2 per device) × volume per conductor
| Wire size | Volume per conductor |
|---|---|
| 14 AWG | 2 in³ |
| 12 AWG | 2.25 in³ |
| 10 AWG | 2.5 in³ |
| 8 AWG | 3 in³ |
| 6 AWG | 5 in³ |
Worked example
A box with four 12 AWG conductors, two grounds, one receptacle and one internal clamp counts as 4 + 1 + 1 + 2 = 8 conductors. At 2.25 in³ each, it needs at least 18 in³.
Use the volume for the largest conductor in the box. Fixture studs, hickeys and wires that pass through without a splice have their own rules in 314.16(B).
Questions
How many wires can go in a box?
Divide the box's marked volume by the volume per conductor for the wire size, then subtract the allowances for grounds, clamps and devices.
Do grounds count toward box fill?
Yes. All equipment grounding conductors together count as one conductor, at the volume of the largest one.