Free trade calculators › Voltage drop calculator

Voltage drop calculator

Enter the load, one-way distance and wire size. Get the voltage drop in volts and percent.

  • Free, no sign-up
  • Built for your phone
  • Same math as the FieldLoom app
Enter your readingsResults update as you type

How to calculate voltage drop

VD = (2 × K × I × L) ÷ CM · three phase: 1.732 instead of 2

K is the conductor's resistivity (12.9 ohm-cmil/ft for copper, 21.2 for aluminum at 75°C), I is the load in amps, L is the one-way length in feet and CM is the wire's area in circular mils.

Worked example

A 20 A load at the end of a 100 ft run of 12 AWG copper on 240 V drops 7.90 V, which is 3.3% of 240 V. Moving up to 10 AWG brings it down to 4.97 V (2.1%).

How much voltage drop is acceptable?

Voltage dropGuidance
3% or lessBranch circuit, NEC recommendation
5% or lessFeeder plus branch circuit combined
More than 5%Upsize the wire or shorten the run

The NEC voltage drop figures are informational notes, not requirements, but most specs and inspectors expect them. Size for ampacity first, then check voltage drop.

Questions

What is the maximum voltage drop allowed by the NEC?

The NEC recommends no more than 3% on a branch circuit and 5% for the feeder and branch circuit together. They're informational notes, not hard limits.

Is distance one way or round trip?

Enter the one-way distance. The formula's 2 accounts for the trip out and back on single-phase circuits.