How to calculate voltage drop
K is the conductor's resistivity (12.9 ohm-cmil/ft for copper, 21.2 for aluminum at 75°C), I is the load in amps, L is the one-way length in feet and CM is the wire's area in circular mils.
A 20 A load at the end of a 100 ft run of 12 AWG copper on 240 V drops 7.90 V, which is 3.3% of 240 V. Moving up to 10 AWG brings it down to 4.97 V (2.1%).
How much voltage drop is acceptable?
| Voltage drop | Guidance |
|---|---|
| 3% or less | Branch circuit, NEC recommendation |
| 5% or less | Feeder plus branch circuit combined |
| More than 5% | Upsize the wire or shorten the run |
The NEC voltage drop figures are informational notes, not requirements, but most specs and inspectors expect them. Size for ampacity first, then check voltage drop.
Questions
What is the maximum voltage drop allowed by the NEC?
The NEC recommends no more than 3% on a branch circuit and 5% for the feeder and branch circuit together. They're informational notes, not hard limits.
Is distance one way or round trip?
Enter the one-way distance. The formula's 2 accounts for the trip out and back on single-phase circuits.