Free trade calculators › Wire size calculator

Wire size calculator

Enter the load and how it's wired. Get the wire gauge and breaker size.

  • Free, no sign-up
  • Built for your phone
  • Same math as the FieldLoom app
Enter your readingsResults update as you type
More than 3 derates the ampacity (NEC 310.15(C)(1)).

How wire size is picked

  1. Continuous loads (3 hours or more) are multiplied by 125%.
  2. With more than 3 current-carrying conductors in a raceway, the ampacity is derated (80% for 4–6, 70% for 7–9, 50% for 10–20).
  3. The breaker is the next standard size at or above the load (× 125% if continuous).
  4. The wire is the smallest size whose NEC Table 310.16 ampacity covers the adjusted load and that's allowed on that breaker.

The small-conductor rule (NEC 240.4(D))

ConductorLargest breaker
14 AWG copper15 A
12 AWG copper20 A
10 AWG copper30 A
12 AWG aluminum15 A
10 AWG aluminum25 A
Worked example

An 18 A load on copper with 75°C insulation needs a 20 A breaker. 14 AWG is rated 20 A in the 75°C column, but 240.4(D) limits it to a 15 A breaker, so the answer is 12 AWG on a 20 A breaker. A 32 A continuous load is 40 A after the 125% factor: 8 AWG on a 40 A breaker.

Terminals are often rated 60°C or 75°C, which can limit you to that column even with 90°C wire. Check the equipment nameplate (MCA and MOCP) for HVAC equipment, and your local code.

Questions

What size wire for a 20 amp circuit?

12 AWG copper. 14 AWG copper is limited to a 15 A breaker by NEC 240.4(D).

What size wire for a 30 amp circuit?

10 AWG copper for most 30 A circuits, the largest breaker 240.4(D) allows on 10 AWG.