Delta T calculator

Enter return and supply air temperatures. Get the temperature split across the evaporator coil.

  • Free, no sign-up
  • Built for your phone
  • Same math as the FieldLoom app
Enter your readingsResults update as you type

How to calculate delta T

Delta T = return air temperature − supply air temperature
  1. Run the system in cooling for 10–15 minutes.
  2. Measure return air temperature at the return, before the coil.
  3. Measure supply air temperature in the supply plenum, after the coil and out of sight of the coil.
  4. Subtract supply from return.
Worked example

Return air is 75°F and supply air is 56°F. Delta T is 75 − 56 = 19°F, which is in range (16–22°F).

What high or low delta T means

Low delta T: common causes are low charge, too much airflow, or a high indoor humidity load (more of the system's capacity goes to removing moisture).

High delta T: usually low airflow, from a dirty filter, dirty coil, or restricted ducts.

Delta T is a quick check, not a charging method. Humid homes often run a lower split even when the system is healthy.

Questions

What is a good delta T for AC?

Most residential systems run a 16–22°F split in cooling with normal humidity and airflow.

Can I charge a system by delta T?

No. Use superheat or subcooling for charge. Delta T helps you spot airflow and humidity problems.

More free HVAC tools