Free HVAC tools › Total external static pressure calculator

Total external static pressure calculator

Enter supply and return static readings. Get total external static pressure and compare it with the rated maximum.

  • Free, no sign-up
  • Built for your phone
  • Same math as the FieldLoom app
Enter your readingsResults update as you type
Enter it as read. The sign doesn't matter.
From the data plate. 0.5 in. WC is common for residential equipment.

How to calculate total external static pressure

TESP = |supply static| + |return static|
  1. Run the blower at the speed you're testing (cooling speed is usual).
  2. Read return static between the filter and the blower.
  3. Read supply static on the supply side of the unit. If the coil is a separate box, the manufacturer's instructions say whether to read before or after it.
  4. Add the two readings, ignoring the signs.
Worked example

Supply reads +0.30 in. WC and return reads −0.25 in. WC. TESP is 0.30 + 0.25 = 0.55 in. WC, above a 0.5 in. WC rating.

What high static pressure means

High static means the blower is fighting the duct system. Airflow drops, coils freeze or heat exchangers run hot, and ECM motors work harder. Look for dirty filters or coils, undersized or restricted ducts, and closed dampers.

Questions

What is a normal total external static pressure?

Most residential furnaces and air handlers are rated for 0.5 in. WC. Check the data plate for the equipment you're testing.