Free HVAC tools › Furnace temperature rise calculator

Furnace temperature rise calculator

Enter return and supply air temperatures and the nameplate rise range. Check the furnace is within spec.

  • Free, no sign-up
  • Built for your phone
  • Same math as the FieldLoom app
Enter your readingsResults update as you type

How to calculate temperature rise

Temperature rise = supply air temperature − return air temperature
  1. Run the furnace in heating for 10–15 minutes so temperatures settle.
  2. Measure return air temperature before the furnace.
  3. Measure supply air temperature in the supply plenum, out of line of sight of the heat exchanger.
  4. Compare the rise with the range on the furnace nameplate (for example 35–65°F).
Worked example

Return air is 68°F and supply air is 118°F. The rise is 118 − 68 = 50°F, inside a 35–65°F nameplate range.

What a high or low rise means

High rise: not enough air is moving across the heat exchanger. Check the filter, closed registers, and return sizing, or the furnace may be overfired. A high rise can overheat and crack the heat exchanger.

Low rise: too much airflow or underfiring, often from low gas pressure.

Questions

Where do I find the temperature rise range?

It's printed on the furnace rating plate, usually inside the blower door, as a range such as 35–65°F or 30–60°F.

More free HVAC tools