HVAC inspection checklists (PDF)

Eight printable tune-up and inspection sheets with reading blanks and target ranges, pulled from the FieldLoom app’s templates.

  • Free, no sign-up
  • Built for your phone
  • Same math as the FieldLoom app

Eight printable HVAC checklists, with the readings

Air conditioner, heat pump, ductless mini-split, gas furnace, electric furnace, water heater, ductwork and indoor air quality. 353 items, 107 of them readings with the target range printed beside the blank. Free, no sign-up.

Download the PDF Letter size, prints in black and white.

Rather type it? Make the finished report online, with the math done and pass/fail marked.

Most free HVAC checklists are a column of checkboxes: “ensure superheat and subcooling are correct”, with nowhere to write the pressure or the line temperature. A box says you looked. A reading says what you found. These sheets come from the templates inside the FieldLoom app, so every reading has its unit and target, safety items are flagged, and the lines marked auto in app are the ones the app calculates for you.

Preview

Free from FieldLoom · fieldloom.io

HVAC Inspection Checklists

Eight tune-up and inspection sheets with the readings, target ranges and pass / fail marks that a checkbox list leaves out. Pulled from the same templates the FieldLoom app runs on the job.

Readings, not checkboxes

  • “Superheat and subcooling correct” is an opinion. 118 PSIG, 52°F line, R-410A, superheat 9°F, pass is a record that holds up in a warranty claim or a dispute.
  • Every numeric line has its target beside it: the same ranges the app grades against (TXV superheat 8–12°F, delta T 16–22°F, furnace CO under 50 ppm in the flue, static 0.3–0.7 in. WC).
  • Lines tagged Safety stop the job when they fail. Lines marked auto in app are calculated for you when you run the checklist in FieldLoom.
  • 1Air Conditioner Tune-Up23 items · 10 readings
  • 2Heat Pump Seasonal68 items · 22 readings
  • 3Ductless Mini-Split Maintenance57 items · 14 readings
  • 4Gas Furnace Tune-Up58 items · 14 readings
  • 5Electric Furnace Tune-Up52 items · 17 readings
  • 6Water Heater Inspection28 items · 6 readings
  • 7Duct Inspection33 items · 13 readings
  • 8Indoor Air Quality Assessment34 items · 11 readings
PassFailN/A tick one write the reading * required for a complete report

How to use these sheets

  1. One sheet per unit. Fill in the make, model and serial before you start; the report is worthless without them.
  2. Write the reading first, then judge it against the target. Never the other way round.
  3. A failed Safety line means the system is not left running until it is fixed or the customer signs off in writing.
  4. Hand the customer a report, not this sheet. In FieldLoom the same checklist becomes a branded PDF with photos, findings and a signature, and the math is done for you.

© 2026 FieldLoom LLC · https://fieldloom.io/tools/hvac-inspection-checklist/ · Reference only. Always follow the equipment manufacturer’s instructions and local code.

1

Air Conditioner Tune-Up

Split or packaged cooling: airflow, outdoor unit, refrigerant circuit.

23 items · 10 readings · 6 calculated for you in the app
CustomerAddressDateTechnicianMake / model / serial

AIRAir Side

Air filter — conditionPassFailN/A
Air filter — replacedPassFailN/A
Supply air temp°F
Return air temp°F
Delta T (supply − return)°Fauto in app16–22°F

OUTOutdoor Unit

Condenser coil — cleanedPassFailN/A
Compressor ampsA
Capacitor — run (µF reading)µF
Capacitor — rated (µF)µF
Capacitor within tolerance?PassFailN/A±6% of rated value
Evidence of refrigerant leakPassFailN/A

REFRefrigerant Readings

Refrigerant typeR-22R-410AR-32R-454BR-407CR-134aOther
Suction line pressure (low-side)PSI
Suction line saturation temp°Fauto in app
Suction line temperature (actual)°F
Superheat (calculated)°Fauto in appTXV: 8–12°F, Piston: 10–20°F
Discharge (head) pressurePSI
Liquid line saturation temp°Fauto in app
Liquid line temperature (actual)°F
Subcooling (calculated)°Fauto in appTXV: 10–18°F, Piston: 5–10°F
Refrigerant addedlbs

ENDCloseout

Overall system conditionExcellentGoodFairNeeds AttentionDo Not Operate
Technician notes
2

Heat Pump Seasonal

Cooling or heating mode: reversing valve, defrost, aux heat, full refrigerant chain.

68 items · 22 readings · 6 calculated for you in the app
CustomerAddressDateTechnicianMake / model / serial

EThermostat & Controls

System cycles on/off normallyPassFailN/A
Emergency heat testedPassFailN/A
Balance point / lockout settings verifiedPassFailN/A
Thermostat typeManualProgrammableSmart

DIndoor Air Handler

Air filter — conditionPassFailN/A
Air filter — replacedPassFailN/A
Air filter size
Air filter MERV rating
Supply air temp°F
Return air temp°F
Delta T (supply − return)°Fauto in app16–22°F
Evaporator coil — cleanPassFailN/A
Condensate drain — clearPassFailN/A
Condensate drain — flushedPassFailN/A
Condensate safety switch / floatPassFailN/A
Drain pan conditionPassFailN/ANo cracks, rust, or standing water
Blower wheel — cleanPassFailN/A
Blower motor conditionPassFailN/A
Blower motor ampsA
Electrical connections — tightPassFailN/A
Ductwork visible — no leaksPassFailN/A

AOutdoor Unit

Coil conditionPassFailN/A
Coil — cleanedPassFailN/A
Compressor ampsA
Compressor RLAA
Run capacitor (µF)µF
Rated capacitor (µF)µF
Capacitor within tolerance?PassFailN/A±6% of rated value
Contactor — conditionPassFailN/A
Contactor voltage L1–L2V
Fan blade conditionPassFailN/A
Fan motor ampsA
Fan motor rated ampsA
Unit base/pad — level and securePassFailN/A
Clearance around unitPassFailN/A12" sides, 24" service, 48" above
Electrical connections — tightPassFailN/A

BReversing Valve & Defrost

Reversing valve — shifts cleanlyPassFailN/A
Reversing valve solenoid — energized in correct modePassFailN/A
Auxiliary / strip heat — operationalPassFailN/A
Defrost cycle testedPassFailN/A
Defrost cycle — terminates properlyPassFailN/A
Defrost board — presentYesNo
Defrost initiation typeTime/TemperatureDemandPressure Differential
Outdoor coil temp during defrost°F
Aux heat lockout setpoint°FTypically 35°F outdoor

CRefrigerant Circuit

Operating mode at time of readingCoolingHeating
Suction line locationIndoor (Cooling Mode)Outdoor (Heating Mode)
Refrigerant typeR-22R-410AR-32R-454BR-407CR-134aOther
Metering device typeTXVEEVFixed Orifice / Piston
Suction line pressure (low-side)PSI
Suction line saturation temp°Fauto in app
Suction line temperature (actual)°F
Superheat (calculated)°Fauto in appTXV: 8–12°F, Piston: 10–20°F
Superheat — target°F
Discharge (head) pressurePSI
Liquid line saturation temp°Fauto in app
Liquid line temperature (actual)°F
Subcooling (calculated)°Fauto in appTXV: 10–18°F, Piston: 5–10°F
Subcooling — target°F
Refrigerant charge statusProperLow — AddedLow — Leak FoundOvercharged
Refrigerant addedlbs
Technician EPA 608 certification number

FOverall System Assessment

Overall system conditionExcellentGoodFairNeeds AttentionDo Not Operate
Technician notes
System age (years)yrs
Estimated remaining life10+ yrs5–10 yrs1–5 yrsEnd of life
Recommended next service
Estimated repair / follow-up cost$
3

Ductless Mini-Split Maintenance

Indoor heads, outdoor unit, inverter refrigerant circuit, controls.

57 items · 14 readings · 5 calculated for you in the app
CustomerAddressDateTechnicianMake / model / serial

AIndoor Heads

Number of indoor headsheads
Air filters — cleaned (every head)PassFailN/A
Air filter — conditionPassFailN/A
Indoor coil — cleanedPassFailN/A
Indoor coil — no ice, damage or heavy biofilmPassFailN/A
Blower wheel — cleanPassFailN/A
Louver / vane motor — operationalPassFailN/A
Condensate line — flushedPassFailN/A
Condensate pump — operationalPassFailN/A
Indoor housing / mounting — securePassFailN/A
Mold or odor presentYesNo
Remote batteries / wall controller — workingPassFailN/A

BOutdoor Unit

Outdoor coil — cleanedPassFailN/A
Coil fins — conditionPassFailN/A
Fan motor — operation, no vibrationPassFailN/A
Fan motor ampsA
Compressor ampsA
Compressor RLA (nameplate)A
Unit level, secure, clear of debrisPassFailN/A
Clearance around unitPassFailN/APer manufacturer, typically 12" sides, 24" front
Line set insulation — intactPassFailN/A
Flare connections — no oil residue (leak sign)SafetyPassFailN/A
Line voltage at outdoor unitV
Electrical connections — tightPassFailN/A
Disconnect installed within sight of outdoor unitPassFailN/A

CRefrigerant Circuit

Operating mode at time of readingCoolingHeating
Refrigerant typeR-410AR-32R-454BR-22Other
Metering device typeEEVTXVFixed Orifice / Piston
Suction line pressure (low-side)PSI
Suction line saturation temp°Fauto in app
Suction line temperature (actual)°F
Superheat (calculated)°Fauto in appInverter EEV: 8–12°F typical, see manufacturer
Discharge (head) pressurePSI
Liquid line saturation temp°Fauto in app
Liquid line temperature (actual)°F
Subcooling (calculated)°Fauto in appInverter EEV: 10–18°F typical, see manufacturer
Supply air temp°F
Return air temp°F
Delta T (supply − return)°Fauto in app16–22°F cooling
Refrigerant charge statusProperLow — AddedLow — Leak FoundOvercharged
Refrigerant addedoz
Technician EPA 608 certification number

DControls & Operation

All modes tested (cool / heat / dry / fan)PassFailN/A
Reversing valve — shifts cleanlyPassFailN/A
Defrost cycle testedPassFailN/A
Control board — no fault codesPassFailN/A
Active fault codes
Communication wire connected (outdoor ↔ indoor)PassFailN/A
Wi-Fi / app control workingPassFailN/A
No abnormal vibration or noisePassFailN/A
Filter cleaning schedule communicatedYesNo

EOverall System Assessment

Overall system conditionExcellentGoodFairNeeds AttentionDo Not Operate
Technician notes
System age (years)yrs
Estimated remaining life10+ yrs5–10 yrs1–5 yrsEnd of life
Recommended next service
Estimated repair / follow-up cost$
4

Gas Furnace Tune-Up

Combustion safety first: CO, gas pressure, heat exchanger, then rise and static.

58 items · 14 readings · 1 calculated for you in the app
CustomerAddressDateTechnicianMake / model / serial

ACombustion & Safety

Carbon monoxide — ambient spaceSafetyppm0 ppm
Gas leak check (soap test)SafetyPassFailN/A
Fuel typeNatural GasPropaneOil
Heat exchanger — visual inspectionSafetyPassFailN/A
Heat exchanger — evidence of cracksSafetyYesNo
Heat exchanger — match/smoke test performedPassFailN/A
Gas pressure — manifoldin. WCNG: 3.2–3.7, LP: 10–11
Gas pressure — supply (incoming)in. WCNG: 5–7, LP: 11–14
Carbon monoxide (CO) level — flueSafetyppm<50 ppm in flue; >200 ppm warrants shutdown
Flue / vent pipe — secure, no leaksPassFailN/A
Flue / vent pipe — proper slopePassFailN/AMin 1/4" per foot upward
Combustion air supply — adequatePassFailN/A
CO detector present in homeYesNo

BBurner & Ignition System

Burner flame colorBlue (Normal)Yellow/Orange (Abnormal)Lazy (Problem)
Burner flame — stable, no rolloutPassFailN/A
Flame sensor — cleanedPassFailN/A
Flame sensor microamps readingµA≥1.5 µA
Burners — cleanedPassFailN/A
Burner typeHot Surface IgnitorSpark IgnitorStanding Pilot
Hot surface ignitor — conditionPassFailN/A
Gas valve — conditionPassFailN/A
Inducer motor — operationPassFailN/A
Pilot assembly — conditionPassFailN/A
Draft pressure (if measured)in. WC

CHeat Exchanger & Airflow

Air filter — conditionPassFailN/A
Air filter — replacedPassFailN/A
Air filter size
Air filter MERV rating
Supply air temperature°F
Return air temperature°F
Temperature rise (Delta T)°Fauto in appPer nameplate (typically 40–70°F)
Nameplate temperature rise range
Temperature rise within spec?PassFailN/A
Static pressure (TESP)in. WC0.3–0.7 in. WC

DBlower & Electrical

Control board — no fault codesPassFailN/A
Active fault codes
Blower wheel — cleanPassFailN/A
Blower motor — conditionPassFailN/A
Blower motor ampsA
Blower motor typePSCECMVariable Speed
High-limit switch testedPassFailN/A
Rollout switch testedPassFailN/A
Pressure switch testedPassFailN/A
Electrical connections — tightPassFailN/A
Blower motor lubricatedPassFailN/A
Belt conditionPassFailN/A

EHumidifier

Humidifier presentYesNo
Humidifier typeBypassFan-PoweredSteam
Humidifier pad — replacedPassFailN/A
Water panel / distribution tray — cleanPassFailN/A
Humidistat set point% RH
Solenoid valve — operationalPassFailN/A

FOverall System Assessment

Overall system conditionExcellentGoodFairNeeds AttentionDo Not Operate
Technician notes
System age (years)yrs
Estimated remaining life10+ yrs5–10 yrs1–5 yrsEnd of life
Recommended next service
Estimated repair / follow-up cost$
5

Electric Furnace Tune-Up

Strip heat and air handlers: voltages, heat strips, sequencers, rise, static.

52 items · 17 readings · 1 calculated for you in the app
CustomerAddressDateTechnicianMake / model / serial

AElectrical Supply & Safety

Line voltage at unit (L1–L2)V228–252 V (240 V ±5%)
Control voltage at thermostat terminals (R–C)V24–28 V
Breaker sizeA
Wire gauge correct for breaker/distancePassFailN/A
Fuses / internal breakers — conditionPassFailN/A
Disconnect within sight of unitPassFailN/A
Electrical connections — tightPassFailN/A
Ground wire connectedSafetyPassFailN/A
Burn marks or discoloration at terminalsSafetyYesNo
Unit cabinet — no signs of overheatingSafetyPassFailN/A

BHeat Strips & Sequencers

Number of heat strip stagesstages
Nameplate heating capacitykW
Heat strips — visual condition (corrosion, pitting, burns)SafetyPassFailN/A
Heat strip continuity — all elementsPassFailN/A
Stage 1 amp drawA
Stage 2 amp drawA
Stage 3 amp drawA
Total heating amps — all stagesAWithin nameplate (kW × 1000 ÷ V)
Sequencers / relays — stages energize in orderPassFailN/A
Time delay between stagessecTypically 30–90 sec
High-limit switch testedSafetyPassFailN/A
Thermal fuse / limit links — intactSafetyPassFailN/A

CBlower & Airflow

Air filter — conditionPassFailN/A
Air filter — replacedPassFailN/A
Air filter size
Air filter MERV rating
Blower wheel — cleanPassFailN/A
Blower motor — conditionPassFailN/A
Blower motor ampsA
Blower motor typePSCECMVariable Speed
Supply air temperature°F
Return air temperature°F
Temperature rise (Delta T)°Fauto in appPer nameplate (typically 30–60°F)
Nameplate temperature rise range
Static pressure (TESP)in. WC0.3–0.7 in. WC
Ductwork visible — no leaksPassFailN/A

DControls & Operation

Thermostat typeManualProgrammableSmart
Thermostat call for heat — all stages respondPassFailN/A
Blower runs with heat callPassFailN/A
Emergency / auxiliary heat mode tested (heat pump systems)PassFailN/A
Control board — no fault codesPassFailN/A
Active fault codes
Humidifier presentYesNo
Humidifier pad — replacedPassFailN/A
No burning smell or abnormal noise on startupSafetyPassFailN/A
System cycles on/off normallyPassFailN/A

EOverall System Assessment

Overall system conditionExcellentGoodFairNeeds AttentionDo Not Operate
Technician notes
System age (years)yrs
Estimated remaining life10+ yrs5–10 yrs1–5 yrsEnd of life
Recommended next service
Estimated repair / follow-up cost$
6

Water Heater Inspection

Tank and tankless, gas or electric: T&P, venting, temperature, anode, flush.

28 items · 6 readings
CustomerAddressDateTechnicianMake / model / serial

AUnit Information

Water heater typeTank (Gas)Tank (Electric)Tankless (Gas)Tankless (Electric)Heat Pump
Manufacturer
Model number
Serial number
Age (years)yrs
Capacity (gallons)gal
BTU / wattage input

BSafety

T&P relief valve — present and operationalSafetyPassFailN/A
T&P discharge pipe — routed to drainSafetyPassFailN/A
Expansion tank — presentPassFailN/A
Expansion tank — pressure correctPassFailN/A
Seismic straps (if required)PassFailN/A
Proper venting / combustion airPassFailN/A
CO detector in vicinityPassFailN/A
Gas leak test — passedSafetyPassFailN/A
Drip pan and drain — presentPassFailN/A
Water supply shutoff — operationalPassFailN/A

CPerformance

Temperature at tap°F120°F recommended
Thermostat setting°F
Anode rod — conditionGoodFairReplaceNot Checked
Sediment flush performedPassFailN/A
Burner / element — conditionPassFailN/A
Flue / vent — conditionPassFailN/A
Water connections — no leaksPassFailN/A
Unit exterior — corrosionPassFailN/A

DFindings & Recommendations

Overall conditionGoodFairPoorReplace Recommended
Technician notes
Estimated repair / follow-up cost$
7

Duct Inspection

Static pressure, leakage, insulation, registers and returns.

33 items · 13 readings · 2 calculated for you in the app
CustomerAddressDateTechnicianMake / model / serial

AVisual Inspection

Duct material typeSheet MetalFlex DuctDuctboardMixed
Duct insulation conditionSafetyPassFailN/A
Visible mold or moistureSafetyYesNo
Visible damage or disconnectionsSafetyYesNo
Duct support and hangersPassFailN/A
Accessible joints sealedPassFailN/A
Return air pathway adequatePassFailN/A
Photos of ductwork conditionPhoto taken

BAirflow Measurements

Blower fan speed settingLowMediumHighAuto
Total system CFM (measured)CFM
Design CFM per tonCFM/ton
Supply static pressurein. WC
Return static pressurein. WC
Total external static pressurein. WCauto in app≤ 0.50 in. WC
Filter pressure dropin. WC
Equipment rated static pressurein. WC

CRegister Readings

Number of supply registers
Number of return grilles
Lowest room CFM measuredCFM
Highest room CFM measuredCFM
Room-to-room temp balance within 3°FPassFailN/A≤ 3°F room-to-room
All registers open and unobstructedPassFailN/A

DDuct Leakage Testing

Test methodDuct BlasterPressure PanVisual Only
Total duct leakageCFM25
Duct leakage to outsideCFM25
Leakage as percent of system CFM%auto in app≤ 8% new construction, ≤ 12% existing
Major leak locations identified
Photos of leak locationsPhoto taken

ERecommendations

Duct sealing recommendedYesNo
Duct replacement recommendedYesNo
Insulation upgrade recommendedYesNo
Additional notes
Estimated repair / follow-up cost$
8

Indoor Air Quality Assessment

Humidity, filtration, ventilation, CO and the equipment that treats the air.

34 items · 11 readings
CustomerAddressDateTechnicianMake / model / serial

ATemperature & Humidity

Indoor temperature°F
Indoor relative humidity%RH30–50%
Outdoor temperature°F
Outdoor relative humidity%RH
Condensation on windows or surfacesYesNo
Visible mold growth anywhereSafetyYesNo

BAir Quality Readings

CO2 levelppm< 1000 ppm
CO levelSafetyppm< 9 ppm
PM2.5µg/m³< 12 µg/m³
VOC levelppb< 500 ppb
Radon level (if applicable)pCi/L< 4.0 pCi/L
Test equipment used

CVentilation

Fresh air intake presentYesNo
Fresh air damper operationalPassFailN/A
Exhaust fans operationalPassFailN/A
Bathroom exhaust vented to outsideSafetyPassFailN/A
Kitchen exhaust vented to outsideSafetyPassFailN/A
ERV/HRV presentYesNo
ERV/HRV filter conditionPassFailN/A

DFiltration & Purification

Filter typeFiberglassPleatedHEPAElectrostaticWashable
Filter MERV ratingMERV 8 minimum recommended
Filter size
Filter conditionNewGoodDirtyNeeds Replacement
UV germicidal light installedYesNo
UV bulb conditionPassFailN/A
Air purifier / ionizer installedYesNo
Air purifier conditionPassFailN/A

EObservations & Recommendations

Odors detectedPassFailN/A
Dust accumulation levelMinimalModerateHeavy
Pet dander concernsYesNo
Recent renovation or constructionYesNo
IAQ improvement recommendations
Photos of IAQ concernsPhoto taken
Estimated repair / follow-up cost$

Why the readings matter

  • Warranty and disputes. A manufacturer’s claim or an unhappy customer six months later is settled by the startup readings, not by a tick mark.
  • Repairs that sell themselves. A delta T of 11°F next to a target of 16–22°F explains the dirty coil better than any pitch.
  • Trends. The same readings every visit show a compressor drawing more amps each year before it fails.