Eight printable HVAC checklists, with the readings
Air conditioner, heat pump, ductless mini-split, gas furnace, electric furnace, water heater, ductwork and indoor air quality. 353 items, 107 of them readings with the target range printed beside the blank. Free, no sign-up.
Download the PDF Letter size, prints in black and white.
Rather type it? Make the finished report online, with the math done and pass/fail marked.
Most free HVAC checklists are a column of checkboxes: “ensure superheat and subcooling are correct”, with nowhere to write the pressure or the line temperature. A box says you looked. A reading says what you found. These sheets come from the templates inside the FieldLoom app, so every reading has its unit and target, safety items are flagged, and the lines marked auto in app are the ones the app calculates for you.
Preview
Free from FieldLoom · fieldloom.io
HVAC Inspection Checklists
Eight tune-up and inspection sheets with the readings, target ranges and pass / fail marks that a checkbox list leaves out. Pulled from the same templates the FieldLoom app runs on the job.
Readings, not checkboxes
- “Superheat and subcooling correct” is an opinion. 118 PSIG, 52°F line, R-410A, superheat 9°F, pass is a record that holds up in a warranty claim or a dispute.
- Every numeric line has its target beside it: the same ranges the app grades against (TXV superheat 8–12°F, delta T 16–22°F, furnace CO under 50 ppm in the flue, static 0.3–0.7 in. WC).
- Lines tagged Safety stop the job when they fail. Lines marked auto in app are calculated for you when you run the checklist in FieldLoom.
- 1Air Conditioner Tune-Up23 items · 10 readings
- 2Heat Pump Seasonal68 items · 22 readings
- 3Ductless Mini-Split Maintenance57 items · 14 readings
- 4Gas Furnace Tune-Up58 items · 14 readings
- 5Electric Furnace Tune-Up52 items · 17 readings
- 6Water Heater Inspection28 items · 6 readings
- 7Duct Inspection33 items · 13 readings
- 8Indoor Air Quality Assessment34 items · 11 readings
PassFailN/A tick one
write the reading
* required for a complete report
How to use these sheets
- One sheet per unit. Fill in the make, model and serial before you start; the report is worthless without them.
- Write the reading first, then judge it against the target. Never the other way round.
- A failed Safety line means the system is not left running until it is fixed or the customer signs off in writing.
- Hand the customer a report, not this sheet. In FieldLoom the same checklist becomes a branded PDF with photos, findings and a signature, and the math is done for you.
CustomerAddressDateTechnicianMake / model / serial
AIRAir Side
| Air filter — condition | PassFailN/A |
| Air filter — replaced | PassFailN/A |
| Supply air temp | °F |
| Return air temp | °F |
| Delta T (supply − return) | °Fauto in app16–22°F |
OUTOutdoor Unit
| Condenser coil — cleaned | PassFailN/A |
| Compressor amps | A |
| Capacitor — run (µF reading) | µF |
| Capacitor — rated (µF) | µF |
| Capacitor within tolerance? | PassFailN/A±6% of rated value |
| Evidence of refrigerant leak | PassFailN/A |
REFRefrigerant Readings
| Refrigerant type | R-22R-410AR-32R-454BR-407CR-134aOther |
| Suction line pressure (low-side) | PSI |
| Suction line saturation temp | °Fauto in app |
| Suction line temperature (actual) | °F |
| Superheat (calculated) | °Fauto in appTXV: 8–12°F, Piston: 10–20°F |
| Discharge (head) pressure | PSI |
| Liquid line saturation temp | °Fauto in app |
| Liquid line temperature (actual) | °F |
| Subcooling (calculated) | °Fauto in appTXV: 10–18°F, Piston: 5–10°F |
| Refrigerant added | lbs |
ENDCloseout
| Overall system condition | ExcellentGoodFairNeeds AttentionDo Not Operate |
| Technician notes | |
CustomerAddressDateTechnicianMake / model / serial
EThermostat & Controls
| System cycles on/off normally | PassFailN/A |
| Emergency heat tested | PassFailN/A |
| Balance point / lockout settings verified | PassFailN/A |
| Thermostat type | ManualProgrammableSmart |
DIndoor Air Handler
| Air filter — condition | PassFailN/A |
| Air filter — replaced | PassFailN/A |
| Air filter size | |
| Air filter MERV rating | |
| Supply air temp | °F |
| Return air temp | °F |
| Delta T (supply − return) | °Fauto in app16–22°F |
| Evaporator coil — clean | PassFailN/A |
| Condensate drain — clear | PassFailN/A |
| Condensate drain — flushed | PassFailN/A |
| Condensate safety switch / float | PassFailN/A |
| Drain pan condition | PassFailN/ANo cracks, rust, or standing water |
| Blower wheel — clean | PassFailN/A |
| Blower motor condition | PassFailN/A |
| Blower motor amps | A |
| Electrical connections — tight | PassFailN/A |
| Ductwork visible — no leaks | PassFailN/A |
AOutdoor Unit
| Coil condition | PassFailN/A |
| Coil — cleaned | PassFailN/A |
| Compressor amps | A |
| Compressor RLA | A |
| Run capacitor (µF) | µF |
| Rated capacitor (µF) | µF |
| Capacitor within tolerance? | PassFailN/A±6% of rated value |
| Contactor — condition | PassFailN/A |
| Contactor voltage L1–L2 | V |
| Fan blade condition | PassFailN/A |
| Fan motor amps | A |
| Fan motor rated amps | A |
| Unit base/pad — level and secure | PassFailN/A |
| Clearance around unit | PassFailN/A12" sides, 24" service, 48" above |
| Electrical connections — tight | PassFailN/A |
BReversing Valve & Defrost
| Reversing valve — shifts cleanly | PassFailN/A |
| Reversing valve solenoid — energized in correct mode | PassFailN/A |
| Auxiliary / strip heat — operational | PassFailN/A |
| Defrost cycle tested | PassFailN/A |
| Defrost cycle — terminates properly | PassFailN/A |
| Defrost board — present | YesNo |
| Defrost initiation type | Time/TemperatureDemandPressure Differential |
| Outdoor coil temp during defrost | °F |
| Aux heat lockout setpoint | °FTypically 35°F outdoor |
CRefrigerant Circuit
| Operating mode at time of reading | CoolingHeating |
| Suction line location | Indoor (Cooling Mode)Outdoor (Heating Mode) |
| Refrigerant type | R-22R-410AR-32R-454BR-407CR-134aOther |
| Metering device type | TXVEEVFixed Orifice / Piston |
| Suction line pressure (low-side) | PSI |
| Suction line saturation temp | °Fauto in app |
| Suction line temperature (actual) | °F |
| Superheat (calculated) | °Fauto in appTXV: 8–12°F, Piston: 10–20°F |
| Superheat — target | °F |
| Discharge (head) pressure | PSI |
| Liquid line saturation temp | °Fauto in app |
| Liquid line temperature (actual) | °F |
| Subcooling (calculated) | °Fauto in appTXV: 10–18°F, Piston: 5–10°F |
| Subcooling — target | °F |
| Refrigerant charge status | ProperLow — AddedLow — Leak FoundOvercharged |
| Refrigerant added | lbs |
| Technician EPA 608 certification number | |
FOverall System Assessment
| Overall system condition | ExcellentGoodFairNeeds AttentionDo Not Operate |
| Technician notes | |
| System age (years) | yrs |
| Estimated remaining life | 10+ yrs5–10 yrs1–5 yrsEnd of life |
| Recommended next service | |
| Estimated repair / follow-up cost | $ |
CustomerAddressDateTechnicianMake / model / serial
AIndoor Heads
| Number of indoor heads | heads |
| Air filters — cleaned (every head) | PassFailN/A |
| Air filter — condition | PassFailN/A |
| Indoor coil — cleaned | PassFailN/A |
| Indoor coil — no ice, damage or heavy biofilm | PassFailN/A |
| Blower wheel — clean | PassFailN/A |
| Louver / vane motor — operational | PassFailN/A |
| Condensate line — flushed | PassFailN/A |
| Condensate pump — operational | PassFailN/A |
| Indoor housing / mounting — secure | PassFailN/A |
| Mold or odor present | YesNo |
| Remote batteries / wall controller — working | PassFailN/A |
BOutdoor Unit
| Outdoor coil — cleaned | PassFailN/A |
| Coil fins — condition | PassFailN/A |
| Fan motor — operation, no vibration | PassFailN/A |
| Fan motor amps | A |
| Compressor amps | A |
| Compressor RLA (nameplate) | A |
| Unit level, secure, clear of debris | PassFailN/A |
| Clearance around unit | PassFailN/APer manufacturer, typically 12" sides, 24" front |
| Line set insulation — intact | PassFailN/A |
| Flare connections — no oil residue (leak sign)Safety | PassFailN/A |
| Line voltage at outdoor unit | V |
| Electrical connections — tight | PassFailN/A |
| Disconnect installed within sight of outdoor unit | PassFailN/A |
CRefrigerant Circuit
| Operating mode at time of reading | CoolingHeating |
| Refrigerant type | R-410AR-32R-454BR-22Other |
| Metering device type | EEVTXVFixed Orifice / Piston |
| Suction line pressure (low-side) | PSI |
| Suction line saturation temp | °Fauto in app |
| Suction line temperature (actual) | °F |
| Superheat (calculated) | °Fauto in appInverter EEV: 8–12°F typical, see manufacturer |
| Discharge (head) pressure | PSI |
| Liquid line saturation temp | °Fauto in app |
| Liquid line temperature (actual) | °F |
| Subcooling (calculated) | °Fauto in appInverter EEV: 10–18°F typical, see manufacturer |
| Supply air temp | °F |
| Return air temp | °F |
| Delta T (supply − return) | °Fauto in app16–22°F cooling |
| Refrigerant charge status | ProperLow — AddedLow — Leak FoundOvercharged |
| Refrigerant added | oz |
| Technician EPA 608 certification number | |
DControls & Operation
| All modes tested (cool / heat / dry / fan) | PassFailN/A |
| Reversing valve — shifts cleanly | PassFailN/A |
| Defrost cycle tested | PassFailN/A |
| Control board — no fault codes | PassFailN/A |
| Active fault codes | |
| Communication wire connected (outdoor ↔ indoor) | PassFailN/A |
| Wi-Fi / app control working | PassFailN/A |
| No abnormal vibration or noise | PassFailN/A |
| Filter cleaning schedule communicated | YesNo |
EOverall System Assessment
| Overall system condition | ExcellentGoodFairNeeds AttentionDo Not Operate |
| Technician notes | |
| System age (years) | yrs |
| Estimated remaining life | 10+ yrs5–10 yrs1–5 yrsEnd of life |
| Recommended next service | |
| Estimated repair / follow-up cost | $ |
CustomerAddressDateTechnicianMake / model / serial
ACombustion & Safety
| Carbon monoxide — ambient spaceSafety | ppm0 ppm |
| Gas leak check (soap test)Safety | PassFailN/A |
| Fuel type | Natural GasPropaneOil |
| Heat exchanger — visual inspectionSafety | PassFailN/A |
| Heat exchanger — evidence of cracksSafety | YesNo |
| Heat exchanger — match/smoke test performed | PassFailN/A |
| Gas pressure — manifold | in. WCNG: 3.2–3.7, LP: 10–11 |
| Gas pressure — supply (incoming) | in. WCNG: 5–7, LP: 11–14 |
| Carbon monoxide (CO) level — flueSafety | ppm<50 ppm in flue; >200 ppm warrants shutdown |
| Flue / vent pipe — secure, no leaks | PassFailN/A |
| Flue / vent pipe — proper slope | PassFailN/AMin 1/4" per foot upward |
| Combustion air supply — adequate | PassFailN/A |
| CO detector present in home | YesNo |
BBurner & Ignition System
| Burner flame color | Blue (Normal)Yellow/Orange (Abnormal)Lazy (Problem) |
| Burner flame — stable, no rollout | PassFailN/A |
| Flame sensor — cleaned | PassFailN/A |
| Flame sensor microamps reading | µA≥1.5 µA |
| Burners — cleaned | PassFailN/A |
| Burner type | Hot Surface IgnitorSpark IgnitorStanding Pilot |
| Hot surface ignitor — condition | PassFailN/A |
| Gas valve — condition | PassFailN/A |
| Inducer motor — operation | PassFailN/A |
| Pilot assembly — condition | PassFailN/A |
| Draft pressure (if measured) | in. WC |
CHeat Exchanger & Airflow
| Air filter — condition | PassFailN/A |
| Air filter — replaced | PassFailN/A |
| Air filter size | |
| Air filter MERV rating | |
| Supply air temperature | °F |
| Return air temperature | °F |
| Temperature rise (Delta T) | °Fauto in appPer nameplate (typically 40–70°F) |
| Nameplate temperature rise range | |
| Temperature rise within spec? | PassFailN/A |
| Static pressure (TESP) | in. WC0.3–0.7 in. WC |
DBlower & Electrical
| Control board — no fault codes | PassFailN/A |
| Active fault codes | |
| Blower wheel — clean | PassFailN/A |
| Blower motor — condition | PassFailN/A |
| Blower motor amps | A |
| Blower motor type | PSCECMVariable Speed |
| High-limit switch tested | PassFailN/A |
| Rollout switch tested | PassFailN/A |
| Pressure switch tested | PassFailN/A |
| Electrical connections — tight | PassFailN/A |
| Blower motor lubricated | PassFailN/A |
| Belt condition | PassFailN/A |
EHumidifier
| Humidifier present | YesNo |
| Humidifier type | BypassFan-PoweredSteam |
| Humidifier pad — replaced | PassFailN/A |
| Water panel / distribution tray — clean | PassFailN/A |
| Humidistat set point | % RH |
| Solenoid valve — operational | PassFailN/A |
FOverall System Assessment
| Overall system condition | ExcellentGoodFairNeeds AttentionDo Not Operate |
| Technician notes | |
| System age (years) | yrs |
| Estimated remaining life | 10+ yrs5–10 yrs1–5 yrsEnd of life |
| Recommended next service | |
| Estimated repair / follow-up cost | $ |
CustomerAddressDateTechnicianMake / model / serial
AElectrical Supply & Safety
| Line voltage at unit (L1–L2) | V228–252 V (240 V ±5%) |
| Control voltage at thermostat terminals (R–C) | V24–28 V |
| Breaker size | A |
| Wire gauge correct for breaker/distance | PassFailN/A |
| Fuses / internal breakers — condition | PassFailN/A |
| Disconnect within sight of unit | PassFailN/A |
| Electrical connections — tight | PassFailN/A |
| Ground wire connectedSafety | PassFailN/A |
| Burn marks or discoloration at terminalsSafety | YesNo |
| Unit cabinet — no signs of overheatingSafety | PassFailN/A |
BHeat Strips & Sequencers
| Number of heat strip stages | stages |
| Nameplate heating capacity | kW |
| Heat strips — visual condition (corrosion, pitting, burns)Safety | PassFailN/A |
| Heat strip continuity — all elements | PassFailN/A |
| Stage 1 amp draw | A |
| Stage 2 amp draw | A |
| Stage 3 amp draw | A |
| Total heating amps — all stages | AWithin nameplate (kW × 1000 ÷ V) |
| Sequencers / relays — stages energize in order | PassFailN/A |
| Time delay between stages | secTypically 30–90 sec |
| High-limit switch testedSafety | PassFailN/A |
| Thermal fuse / limit links — intactSafety | PassFailN/A |
CBlower & Airflow
| Air filter — condition | PassFailN/A |
| Air filter — replaced | PassFailN/A |
| Air filter size | |
| Air filter MERV rating | |
| Blower wheel — clean | PassFailN/A |
| Blower motor — condition | PassFailN/A |
| Blower motor amps | A |
| Blower motor type | PSCECMVariable Speed |
| Supply air temperature | °F |
| Return air temperature | °F |
| Temperature rise (Delta T) | °Fauto in appPer nameplate (typically 30–60°F) |
| Nameplate temperature rise range | |
| Static pressure (TESP) | in. WC0.3–0.7 in. WC |
| Ductwork visible — no leaks | PassFailN/A |
DControls & Operation
| Thermostat type | ManualProgrammableSmart |
| Thermostat call for heat — all stages respond | PassFailN/A |
| Blower runs with heat call | PassFailN/A |
| Emergency / auxiliary heat mode tested (heat pump systems) | PassFailN/A |
| Control board — no fault codes | PassFailN/A |
| Active fault codes | |
| Humidifier present | YesNo |
| Humidifier pad — replaced | PassFailN/A |
| No burning smell or abnormal noise on startupSafety | PassFailN/A |
| System cycles on/off normally | PassFailN/A |
EOverall System Assessment
| Overall system condition | ExcellentGoodFairNeeds AttentionDo Not Operate |
| Technician notes | |
| System age (years) | yrs |
| Estimated remaining life | 10+ yrs5–10 yrs1–5 yrsEnd of life |
| Recommended next service | |
| Estimated repair / follow-up cost | $ |
CustomerAddressDateTechnicianMake / model / serial
AUnit Information
| Water heater type | Tank (Gas)Tank (Electric)Tankless (Gas)Tankless (Electric)Heat Pump |
| Manufacturer | |
| Model number | |
| Serial number | |
| Age (years) | yrs |
| Capacity (gallons) | gal |
| BTU / wattage input | |
BSafety
| T&P relief valve — present and operationalSafety | PassFailN/A |
| T&P discharge pipe — routed to drainSafety | PassFailN/A |
| Expansion tank — present | PassFailN/A |
| Expansion tank — pressure correct | PassFailN/A |
| Seismic straps (if required) | PassFailN/A |
| Proper venting / combustion air | PassFailN/A |
| CO detector in vicinity | PassFailN/A |
| Gas leak test — passedSafety | PassFailN/A |
| Drip pan and drain — present | PassFailN/A |
| Water supply shutoff — operational | PassFailN/A |
CPerformance
| Temperature at tap | °F120°F recommended |
| Thermostat setting | °F |
| Anode rod — condition | GoodFairReplaceNot Checked |
| Sediment flush performed | PassFailN/A |
| Burner / element — condition | PassFailN/A |
| Flue / vent — condition | PassFailN/A |
| Water connections — no leaks | PassFailN/A |
| Unit exterior — corrosion | PassFailN/A |
DFindings & Recommendations
| Overall condition | GoodFairPoorReplace Recommended |
| Technician notes | |
| Estimated repair / follow-up cost | $ |
CustomerAddressDateTechnicianMake / model / serial
AVisual Inspection
| Duct material type | Sheet MetalFlex DuctDuctboardMixed |
| Duct insulation conditionSafety | PassFailN/A |
| Visible mold or moistureSafety | YesNo |
| Visible damage or disconnectionsSafety | YesNo |
| Duct support and hangers | PassFailN/A |
| Accessible joints sealed | PassFailN/A |
| Return air pathway adequate | PassFailN/A |
| Photos of ductwork condition | Photo taken |
BAirflow Measurements
| Blower fan speed setting | LowMediumHighAuto |
| Total system CFM (measured) | CFM |
| Design CFM per ton | CFM/ton |
| Supply static pressure | in. WC |
| Return static pressure | in. WC |
| Total external static pressure | in. WCauto in app≤ 0.50 in. WC |
| Filter pressure drop | in. WC |
| Equipment rated static pressure | in. WC |
CRegister Readings
| Number of supply registers | |
| Number of return grilles | |
| Lowest room CFM measured | CFM |
| Highest room CFM measured | CFM |
| Room-to-room temp balance within 3°F | PassFailN/A≤ 3°F room-to-room |
| All registers open and unobstructed | PassFailN/A |
DDuct Leakage Testing
| Test method | Duct BlasterPressure PanVisual Only |
| Total duct leakage | CFM25 |
| Duct leakage to outside | CFM25 |
| Leakage as percent of system CFM | %auto in app≤ 8% new construction, ≤ 12% existing |
| Major leak locations identified | |
| Photos of leak locations | Photo taken |
ERecommendations
| Duct sealing recommended | YesNo |
| Duct replacement recommended | YesNo |
| Insulation upgrade recommended | YesNo |
| Additional notes | |
| Estimated repair / follow-up cost | $ |
CustomerAddressDateTechnicianMake / model / serial
ATemperature & Humidity
| Indoor temperature | °F |
| Indoor relative humidity | %RH30–50% |
| Outdoor temperature | °F |
| Outdoor relative humidity | %RH |
| Condensation on windows or surfaces | YesNo |
| Visible mold growth anywhereSafety | YesNo |
BAir Quality Readings
| CO2 level | ppm< 1000 ppm |
| CO levelSafety | ppm< 9 ppm |
| PM2.5 | µg/m³< 12 µg/m³ |
| VOC level | ppb< 500 ppb |
| Radon level (if applicable) | pCi/L< 4.0 pCi/L |
| Test equipment used | |
CVentilation
| Fresh air intake present | YesNo |
| Fresh air damper operational | PassFailN/A |
| Exhaust fans operational | PassFailN/A |
| Bathroom exhaust vented to outsideSafety | PassFailN/A |
| Kitchen exhaust vented to outsideSafety | PassFailN/A |
| ERV/HRV present | YesNo |
| ERV/HRV filter condition | PassFailN/A |
DFiltration & Purification
| Filter type | FiberglassPleatedHEPAElectrostaticWashable |
| Filter MERV rating | MERV 8 minimum recommended |
| Filter size | |
| Filter condition | NewGoodDirtyNeeds Replacement |
| UV germicidal light installed | YesNo |
| UV bulb condition | PassFailN/A |
| Air purifier / ionizer installed | YesNo |
| Air purifier condition | PassFailN/A |
EObservations & Recommendations
| Odors detected | PassFailN/A |
| Dust accumulation level | MinimalModerateHeavy |
| Pet dander concerns | YesNo |
| Recent renovation or construction | YesNo |
| IAQ improvement recommendations | |
| Photos of IAQ concerns | Photo taken |
| Estimated repair / follow-up cost | $ |