How the weigh-in adjustment works
- Read the factory charge and the line set length it covers from the data plate.
- Measure the actual line set length, one way.
- Find the charge per foot for your liquid line size.
- Add (or remove) charge for the difference in length.
A condenser ships with 100 oz for a 25 ft line set. The install uses 50 ft of 3/8" liquid line. That's 25 extra feet × 0.55 oz/ft = 13.75 oz, for a total of 7 lbs 1.8 oz.
Charge per foot of liquid line
| Liquid line | Charge per foot |
|---|---|
| 1/4" | 0.2 oz/ft |
| 5/16" | 0.36 oz/ft |
| 3/8" | 0.55 oz/ft |
| 1/2" | 0.98 oz/ft |
| 5/8" | 1.53 oz/ft |
| 3/4" | 2.2 oz/ft |
| 7/8" | 3 oz/ft |
These are typical values from manufacturer installation guides. Always use the charge-per-foot figure in the installation manual when it's listed, then confirm the charge with superheat or subcooling.
Questions
How much refrigerant do I add per foot of line set?
It depends on the liquid line size. For a 3/8" liquid line, a common figure is about 0.55 oz per foot. Check the installation manual for your unit.
Do I remove refrigerant for a short line set?
Many manufacturers say not to remove charge for line sets shorter than the factory length. Follow the installation manual, and verify with subcooling.